EAN code8595057659551
Customs code72169180
Weight0,10 kg/pcs
Surface finishHot Dip Galvanized
Temperature resistance-50 - 150 °C
Funcionality in fireP90-R, E90, PS90
StandardsČSN EN 61537
Fire resistance standardsČSN 73 0895, DIN 4102-12, STN 92 0205
Thickness of metal sheet1,2 mm
Maximum load100 kg
Dimension A150 mm
Dimension B30 mm
Dimension C15 mm
For width of cable tray100 mm
Outer holes9x35 mm
Inner holes7x32 mm

Suitable for creating of beam for cable traces to be carried on thread rods. The load bearing profile is fixed by using two threaded rods ZT 8 + nut M 8 + washer PD 8.

Note for system with maintained functionality in fire:
You find more information in the catalogue Systems with maintained functionality in fire.