EAN code8595568930316
Customs code72169180
Weight1,15 kg/m
Surface finishPre-Galvanized
Temperature resistance-50 - 150 °C
Length2000 mm
Funcionality in fireP90-R, E90, PS90
StandardsČSN EN 61537
Fire resistance standardsČSN 73 0895, DIN 4102-12, STN 92 0205
Thickness of metal sheet1,2 mm
Dimension A2000 mm
Dimension B30 mm
Dimension C15 mm
Holes9x26 mm

It is used for mounting of cable clamps and thereby for the anchoring of the cables to the ceiling or to the wall.

Note for system with maintained functionality in fire:
Suitable for creating of beam for cable traces to be carried on thread rods. The load bearing profile is fixed by using two threaded rods ZT 8 + nut M 8 + washer PD 8.
You find more information in the catalogue Systems with maintained functionality in fire.

Currently there are no products