EAN code8595568934734
Customs code39259020
Weight0,89 kg/m
Colourwhite
MaterialHF
Halogen free materialyes
Leadless materialyes
Self-extinguishing30 s
Temperature resistance-25 - 90 °C
Flaming loop test850 °C
Mechanical protectionIK07
Impact resistance1 J
Antibacterialyes
Width110 mm
Height67,5 mm
Length2 m
Inside area5500 mm2
Allowance
The trunkings are available in lengths with a tolerance of ± 0.5% at 20 ° C.
Use
they are resistant to aggressive and chemical environments. They do not resist UV radiation, they are not suitable for outdoor use.
Manufactures´s recommendations
If the SK 40X33 (higher) shielding canal can be installed, it is not possible to use instruments with a larger installation depth, eg with an overvoltage protection device. The producer recommends checking the depth of a particular device before installation. To install devices with very round corners, KOPOS recommends using of the KP PK HF instrument box and drilling the hole in the lid using the VPT 64 drill.
Area with explosion danger
Electro-installation trunking (insertive, rectangular, halogen-free) and parapet canals with accesories can be installed in zones with explosion hazard of flammable gases (zone 2) and with the risk of explosion of flammable dusts (zone 22), installation must comply with EN 60079-14.
Fire reaction class of underlying materialA1 - F
Protection typesIP 40
StandardsČSN EN 50 085-1
Fire resistance standardsČSN 73 0895, DIN 4102-12, STN 92 0205
Package descriptionpackage - cardboard
With protective foilyes

Designed for inserting power and communication circuits, security lines and other lines. Individual lines can be electromagnetically shielded by inserting a shielding canal, which is fixed to the trunking by clamps PSK 1. For classical instruments that are installed in a closed instrument box KP 80 PK HF clicked in the body of the canal or into an open instrument box KP PK HF installed in the bottom of the parapet trunkings. With using KOPOBOX MINI P, modular devices can be installed. There is no need to use any covers for the final installation of instrument. The lid is cut to the desired length and inserted next to the instrument.