EAN code8595057631359
Customs code73063041
Weight2,01 kg/m
Materialsteel
Surface finish
ZN: after steel welding hot-dip galvanized using immersion, zinc layer min. 35 micrometers, high corrosion resistance - Group 4
Temperature resistance-45 - 250 °C
Mechanical resistance4000 N/5cm
Mechanical protectionIK10
Length3 m
Outside diameter50 mm
Inner diameter (min.)43,8 mm
Funcionality in fireP90-R, E90, PS90
Thread typeM50 x 1,5
Sorting code55561
StandardsČSN EN 61386-1 ed.2
Fire resistance standardsČSN 73 0895, DIN 4102-12, STN 92 0205
Max. load for fire resistance10 kg

The pipes are suitable for mechanical protection of conductors and cables. Threaded conduits are supplied with one coupler. While using pipes along with bushing 4813/P - 4842/P and 4913 - 4942 is scope of application only -5 - +60 °C.

Note for system with maintained functionality in fire:
max. 1 piece of cable in the pipe
You find more information in the catalogue Systems with maintained functionality in fire.