QUANTITY OF LOADED CABLES


Wiring trunkings and accessories

    CYKY 2x1,5 CYKY 3x1,5 CYKY 4x1,5 CYKY 3x2,5 CYKY 5x1,5 CYKY 4x2,5 CYKY 5x2,5 CYKY 4x4 CYKY 5x4 CYKY 4x6 CYKY 5x6
cabel diametr (mm) 6 8,3 8,7 9,5 10 10,3 10,9 12,3 13,2 14,4 14,4 16
trunkings                        
LV 11X10 1 X X X X X X X X X X X
LV 18X13 2 1 1 1 1 1 1 X X X X X
LV 24X22 7 3 3 3 2 2 2 2 1 1 1 1
LV 40X15 9 5 4 4 3 3 3 2 2 X X X
                         
LZ 15X12 2 1 1 1 X X X X X X X X
LZK 15X12 3 2 1 1 X X X X X X X X
                         
LH 15X10 2 1 1 X X X X X X X X X
LHD 17X17 3 2 2 1 1 1 1 1 X X X X
LHD 20X10 2 1 1 1 1 1 1 1 X X X X
LHD 20X20 4 2 2 2 2 1 1 1 1 1 1 X
LHD 25X15 5 3 2 2 2 2 2 0 0 0 0 X
LHD 25X20 7 3 3 3 2 2 2 2 1 1 0 X
LHD 30X25 8 4 4 3 3 3 3 2 2 1 1 1
LHD 32X15 8 4 4 3 3 3 2 X X X X X
LHD 40X20 9 5 4 4 3 3 3 2 1 1 X X
LHD 40X40 22 11 10 9 8 7 7 5 4 4 4 3
LH 60X40 31 16 15 12 11 11 9 7 6 5 5 4
LH 80X40 40 21 19 16 14 14 12 10 8 7 7 6
                         
LE 40 8 4 4 3 3 3 3 2 2 X X X
LE 60 20 6 6 4 4 4 4 2 2 2 2 2
LE 80 2 6 6 6 6 5 4 2 2 2 2 2
LE 100 30 9 9 6 6 6 6 3 3 3 3 3
                         
EK 100X40 50 26 24 20 18 17 15 12 10 9 9 7
EK 120X40 60 31 29 24 22 20 18 14 12 10 10 8
                         
EKE 60X60 43 23 21 17 16 15 13 10 9 8 8 6
EKE 100X60 77 40 36 31 28 26 23 18 16 13 13 11
EKE 140X60 117 61 55 47 42 40 35 28 24 20 20 16
EKE 180X60 150 78 71 60 54 51 45 36 31 26 26 21
                         
PK 110X70 106 55 50 42 38 36 32 25 22 18 18 15
PK 140X70 138 2 66 55 50 47 42 33 29 24 24 19
PK 110X70 D 92 48 44 37 33 31 28 22 19 16 16 13
PK 140X70 D 120 63 57 48 43 41 36 29 25 21 21 17
PK 170X70 D 155 81 74 62 56 53 47 37 32 27 27 22
PK 120X55 D 62 32 29 25 22 21 19 15 13 11 11 9
PK 160X65 D 123 64 59 49 44 42 37 29 25 21 21 17
                         
LO 35 2 1 1 X X X X X X X X X
LO 50 5 3 2 2 2 2 2 X X X X X
LO 75 7 3 3 3 2 2 2 X X X X X
LP 35 6 3 3 2 2 2 2 1 1 1 1 1
                         
LP 80X25 25 13 12 10 9 8 7 6 5 4 4 3
LPK 80X25 25 13 12 10 9 8 7 6 5 4 4 3
LR 30 9 5 4 4 3 3 3 2 2 2 2 1
L 40 8 4 4 X X X X X X X X X
 
SK 40X20 13 7 6 5 5 4 4 3 3 2 2 2
SK 40X33 20 10 10 8 7 7 6 5 4 3 2 2


If the filling is different, you must take into account the way of mounting and the requirements of ČSN 33 2000-4-43, ČSN 33 2000-4-473 and ČSN 33 2000-5-523 standards. These standards define the current-carrying capacity of the conductors and cables respective to their way of mounting, arrangement and surrounding temperature.

Parapet culverts

placement data cables 6 mm power cables 9,5 mm

full usage of culverts, without boxes

data cables 6 mm power cables 9,5 mm
PK 110X70 D top 10 ks 3 ks 100 ks 40 ks
middle (SK 40X33) 16 ks 9 ks
down 13 ks 8 ks
PK 140X70 D top 15 ks 5 ks 130 ks 50 ks
middle (SK 40X33) 16 ks 9 ks
down 20 ks 10 ks
PK 170X70 D top 20 ks 10 ks 150 ks 60 ks
middle (SK 40X33) 16 ks 9 ks
down 45 ks 15 ks
PK 120X55 D top 23 ks 11 ks 23 ks 11 ks
down 17 ks 7 ks 32 ks 19 ks
PK 160X65 D top 20 ks 8 ks 40 ks 15 ks
down 25 ks 9 ks 50 ks 20 ks


            PK 140X70 D                                   PK 120X55 D                                PK 160X65 D
     

The chart counts with 60 % usage of inner trunking cross-section. If the filling is different, you must take into account the way of mounting and the requirements of ČSN 33 2000-4-43, ČSN 33 2000-4-473 and ČSN 33 2000-5-523 standards. These standards define the current-carrying capacity of the conductors and cables respective to their way of mounting, arrangement and surrounding temperature.

Wiring pipes

    CYKY 2x1,5 CYKY 3x1,5 CYKY 4x1,5 CYKY 3x2,5 CYKY 5x1,5 CYKY 4x2,5 CYKY 5x2,5 CYKY 4x4 CYKY 5x4 CYKY 4x6 CYKY 5x6
cabel diametr (mm) 6 8,3 8,7 9,5 10 10,3 10,9 12,3 13,2 14,4 14,4 16
                         
Flexible pipes
XX16E - EN 1 1 1 X X X X X X X X X
XX20 - EN 2 (3) 1 1 1 1 1 1 X X X X X
XX25 - EN 4 2 2 1 1 1 1 1 1 1 1 X
XX32 - EN 8 4 4 3 3 3 2 1 1 1 1 1
XX40 - EN 13 7 6 5 5 4 4 3 3 2 2 1
XX50 - EN 21 11 10 8 7 7 6 5 4 4 4 3
                         
XX13 - ČSN 2 1 1 1 1 1 1 X X X X X
XX16 - ČSN 3 1(2) 1 1 1 1 1 1 1 X X X
XX23 - ČSN 7 4 3 3 2 2 1(2) 1 1 1 1 1
XX29 - ČSN 11 6 5 4 4 4 3 3 2 1 1 1
XX36 - ČSN 17 9 8 7 6 6 5 4 3 3 3 2
                         
SF 16 3 1 1 1 1 1 1 1 1 X X X
SF 20 5 3 2 1(2) 1 1 1 1 1 1 1 1
SF 25 8 4 4 3 3 3 2(3) 1(2) 1 1 1 1
SF 32 13 7 6 5 5 5 4 3 3 2(3) 2(3) 1(2)
                         
Rigid pipes
XX16E - EN 1(2) 1 1 1 1 1 X X X X X X
XX20 - EN 2 (3) 1 1 1 1 1 1 1 1 X X X
XX25 - EN 6 3 3 2 1(2) 1(2) 1 1 1 1 1 1
XX32 - EN 9 5 4 4 3 3 3 2 1 1 1 1
XX40 - EN 15 8 7 6 6 5 5 4 3 3 3 1(2)
XX50 - EN 24 13 12 10 9 8 7 6 5 4 4 3
XX63 - EN 43 22 20 17 15 14 13 10 9 7 7 6
                         
6013 - ČSN 4 2 1(2) 1 1 1 1 1 1 1 1 X
6016 - ČSN 2 (3) 3 3 1(2) 1 1 1 1 1 1 1 1
6021 - ČSN 9 5 4 3 3 3 3 1(2) 1 1 1 1
6029 - ČSN 15 8 7 6 6 5 5 4 3 3 3 2
6036 - ČSN 25 13 12 10 9 9 8 6 5 4 4 4
6042 - ČSN 34 18 16 14 12 12 10 8 7 6 6 5
                         
6016E - EN 3 1 1 1 1 1 1 1 X X X X
6020 - EN 4 2 1(2) 1 1 1 1 1 1 1 1 X
6025 - EN 7 3 3 3 2 2 1 1 1 1 1 1
6032 - EN 11 6 5 5 4 4 3 3 2 1 1 1
6040 - EN 19 10 9 7 7 6 6 4 4 3 3 3
6050 - EN 30 15 14 12 11 10 9 7 6 5 5 4
6063 - EN 48 25 23 19 17 16 15 11 10 8 8 7


The chart counts with 60 % usage of inner trunking cross-section.



KOPOS KOLÍN a.s., Havlíčkova 432, Kolín IV, 280 94, Czech Republic, phone: +420 321 730 111, e-mail: kopos@kopos.cz                        © 2007 KOPOS KOLÍN a.s., Jan Vrzáček