QUANTITY OF LOADED CABLES


Wiring trunkings

cables construction   2x1,5 3x1,5 4x1,5 3x2,5 5x1,5 4x2,5 5x2,5 4x4 5x4 4x6 5x6
orientation cable diameter (mm) 6 8,3 8,7 9,5 10 10,3 10,9 12,3 13,2 14,4 14,4 16
                         
LV 11X10 1 X X X X X X X X X X X
LV 18X13 2 1 1 1 1 1 1 X X X X X
LV 24X22 7 3 3 3 2 2 2 2 1 1 1 1
LV 40X15 9 5 4 4 3 3 3 2 2 X X X
                         
LH 15X10 2 1 1 X X X X X X X X X
LHD 17X17 3 2 2 1 1 1 1 1 X X X X
LHD 20X10 2 1 1 1 1 1 1 1 X X X X
LHD 20X20 4 2 2 2 2 1 1 1 1 1 1 X
LHD 25X15 5 3 2 2 2 2 2 0 0 0 0 X
LHD 25X20 7 3 3 3 2 2 2 2 1 1 0 X
LHD 30X25 8 4 4 3 3 3 3 2 2 1 1 1
LHD 32X15 8 4 4 3 3 3 2 X X X X X
LHD 40X20 9 5 4 4 3 3 3 2 1 1 X X
LHD 40X40 22 11 10 9 8 7 7 5 4 4 4 3
LH 60X40 31 16 15 12 11 11 9 7 6 5 5 4
                         
LHD 20X10HF 2 1 1 1 1 1 1 1 X X X X
LHD 20X20HF 4 2 2 2 2 1 1 1 1 1 1 X
LHD 40X20HF 9 5 4 4 3 3 3 2 1 1 X X
LHD 40X40HF 22 11 10 9 8 7 7 5 4 4 4 3
EKD 80X40HF 40 21 19 16 14 14 12 10 8 7 7 6
PK 110X70 D HF 100 48 44 40 33 31 28 22 19 16 16 13
                         
LZ 15X12 2 1 1 1 X X X X X X X X
LZK 15X12 3 2 1 1 X X X X X X X X
                         
LP 80X25 25 13 12 10 9 8 7 6 5 4 4 3
LPK 80X25 25 13 12 10 9 8 7 6 5 4 4 3
LP 35 6 3 3 2 2 2 2 1 1 1 1 1
LR 30 9 5 4 4 3 3 3 2 2 2 2 1
                         
LO 35 2 1 1 X X X X X X X X X
LO 50 5 3 2 2 2 2 2 X X X X X
LO 75 7 3 3 3 2 2 2 X X X X X
                         
LE 40 8 4 4 3 3 3 3 2 2 X X X
LE 60 20 6 6 4 4 4 4 2 2 2 2 2
LE 80 2 6 6 6 6 5 4 2 2 2 2 2
LE 100 30 9 9 6 6 6 6 3 3 3 3 3
                         
EKD 80X40 40 21 19 16 14 14 12 10 8 7 7 6
EKD 100X40 50 26 24 20 18 17 15 12 10 9 9 7
EKD 120X40 60 31 29 24 22 20 18 14 12 10 10 8
                         
EKE 60X60 43 23 21 17 16 15 13 10 9 8 8 6
EKE 100X60 77 40 36 31 28 26 23 18 16 13 13 11
EKE 140X60 117 61 55 47 42 40 35 28 24 20 20 16
EKE 180X60 150 78 71 60 54 51 45 36 31 26 26 21
                         
PK 110X70 D 92 48 44 37 33 31 28 22 19 16 16 13
PK 140X70 D 120 63 57 48 43 41 36 29 25 21 21 17
PK 170X70 D 155 81 74 62 56 53 47 37 32 27 27 22
PK 90X55 D 40 21 19 16 14 14 12 10 8 7 7 6
PK 120X55 D 62 32 29 25 22 21 19 15 13 11 11 9
PK 160X65 D 123 64 59 49 44 42 37 29 25 21 21 17
PK 210X70 D 125 65 59 50 45 42 35 30 26 22 22 18
                         
SK 40X20 13 7 6 5 5 4 4 3 3 2 2 2
SK 40X33 20 10 10 8 7 7 6 5 4 3 2 2

The chart counts with 60 % usage of inner trunking cross-section. If the filling is different, you must take into account the way of mounting and the requirements of ČSN 33 2000-4-43, ČSN 33 2000-4-473 and ČSN 33 2000-5-523 standards. These standards define the current-carrying capacity of the conductors and cables respective to their way of mounting, arrangement and surrounding temperature.

Parapet trunkings

placement usage of trunkings with boxes usage of trunkings without boxes
data cables
Ø 6 mm
power cables
Ø 9,5 mm
data cables
Ø 6 mm
power cables
Ø 9,5 mm
PK 110X70 D top 10 pcs 3 pcs 100 pcs 40 pcs
middle (SK 40X33) 16 pcs 9 pcs
down 13 pcs 8 pcs
PK 140X70 D top 15 pcs 5 pcs 130 pcs 50 pcs
middle (SK 40X33) 16 pcs 9 pcs
down 20 pcs 10 pcs
PK 170X70 D top 20 pcs 10 pcs 150 pcs 60 pcs
middle (SK 40X33) 16 pcs 9 pcs
down 45 pcs 15 pcs
PK 90X55 D down 16 pcs 10 pcs 55 pcs 22 pcs
PK 120X55 D top 23 pcs 11 pcs 23 pcs 11 pcs
down 17 pcs 7 pcs 32 pcs 19 pcs
PK 160X65 D top 20 pcs 8 pcs 40 pcs 15 pcs
down 25 pcs 9 pcs 50 pcs 20 pcs
PK 210X70 D top 10 pcs 8 pcs 170 pcs 70 pcs
middle 16 pcs 10 pcs
down 12 pcs 8 pcs


            PK 140X70 D                              PK 90X55 D                              PK 120X55 D
     
            PK 160X65 D                               PK 210X70 D
  

The chart counts with 60 % usage of inner trunking cross-section. If the filling is different, you must take into account the way of mounting and the requirements of ČSN 33 2000-4-43, ČSN 33 2000-4-473 and ČSN 33 2000-5-523 standards. These standards define the current-carrying capacity of the conductors and cables respective to their way of mounting, arrangement and surrounding temperature.

Wiring pipes

    2x1,5 3x1,5 4x1,5 3x2,5 5x1,5 4x2,5 5x2,5 4x4 5x4 4x6 5x6
cabel diametr (mm) 6 8,3 8,7 9,5 10 10,3 10,9 12,3 13,2 14,4 14,4 16
Flexible pipes
XX16E - EN 1 1 1 X X X X X X X X X
XX20 - EN 2 (3) 1 1 1 1 1 1 X X X X X
XX25 - EN 4 2 2 1 1 1 1 1 1 1 1 X
XX32 - EN 8 4 4 3 3 3 2 1 1 1 1 1
XX40 - EN 13 7 6 5 5 4 4 3 3 2 2 1
XX50 - EN 21 11 10 8 7 7 6 5 4 4 4 3
                         
XX13 - ČSN 2 1 1 1 1 1 1 X X X X X
XX16 - ČSN 3 1(2) 1 1 1 1 1 1 1 X X X
XX23 - ČSN 7 4 3 3 2 2 1(2) 1 1 1 1 1
XX29 - ČSN 11 6 5 4 4 4 3 3 2 1 1 1
XX36 - ČSN 17 9 8 7 6 6 5 4 3 3 3 2
                         
SF 16 3 1 1 1 1 1 1 1 1 X X X
SF 20 5 3 2 1(2) 1 1 1 1 1 1 1 1
SF 25 8 4 4 3 3 3 2(3) 1(2) 1 1 1 1
SF 32 13 7 6 5 5 5 4 3 3 2(3) 2(3) 1(2)
                         
KF 09040 13 7 6 5 5 5 4 3 3 2 2 2
KF 09050 22 11 10 9 8 7 7 5 5 4 4 3
KF 09063 35 18 17 14 13 12 11 8 7 6 6 5
KF 09075 49 25 23 19 18 17 15 12 10 8 8 7
KF 09090 74 38 35 29 27 25 22 18 15 13 13 10
KF 09110 116 60 55 46 42 39 35 28 24 20 20 16
KF 09120 131 68 62 52 47 44 40 31 27 23 23 18
KF 09125 153 80 73 61 55 52 46 36 32 27 27 21
KF 09160 242 127 115 97 87 82 73 58 50 42 42 34
KF 09175 295 154 140 117 106 100 89 70 61 51 51 41
Rigid pipes
XX16E - EN 1(2) 1 1 1 1 1 X X X X X X
XX20 - EN 2 (3) 1 1 1 1 1 1 1 1 X X X
XX25 - EN 6 3 3 2 1(2) 1(2) 1 1 1 1 1 1
XX32 - EN 9 5 4 4 3 3 3 2 1 1 1 1
XX40 - EN 15 8 7 6 6 5 5 4 3 3 3 1(2)
XX50 - EN 24 13 12 10 9 8 7 6 5 4 4 3
XX63 - EN 43 22 20 17 15 14 13 10 9 7 7 6
                         
6013 - ČSN 4 2 1(2) 1 1 1 1 1 1 1 1 X
6016 - ČSN 2 (3) 3 3 1(2) 1 1 1 1 1 1 1 1
6021 - ČSN 9 5 4 3 3 3 3 1(2) 1 1 1 1
6029 - ČSN 15 8 7 6 6 5 5 4 3 3 3 2
6036 - ČSN 25 13 12 10 9 9 8 6 5 4 4 4
6042 - ČSN 34 18 16 14 12 12 10 8 7 6 6 5
                         
6016E - EN 3 1 1 1 1 1 1 1 X X X X
6020 - EN 4 2 1(2) 1 1 1 1 1 1 1 1 X
6025 - EN 7 3 3 3 2 2 1 1 1 1 1 1
6032 - EN 11 6 5 5 4 4 3 3 2 1 1 1
6040 - EN 19 10 9 7 7 6 6 4 4 3 3 3
6050 - EN 30 15 14 12 11 10 9 7 6 5 5 4
6063 - EN 48 25 23 19 17 16 15 11 10 8 8 7
                         
KD 09040 13 7 6 5 5 5 4 3 3 2 2 2
KD 09050 22 11 10 9 8 7 7 5 5 4 4 3
KD 09063 35 18 17 14 13 12 11 8 7 6 6 5
KD 09075 49 25 23 19 18 17 15 12 10 8 8 7
KD 09090 74 38 35 29 27 25 22 18 15 13 13 10
KD 09110 116 60 55 46 42 39 35 28 24 20 20 16
KD 09120 131 68 62 52 47 44 40 31 27 23 23 18
KD 09125 153 80 73 61 55 52 46 36 32 27 27 21
KD 09160 242 127 115 97 87 82 73 58 50 42 42 34
KD 09175 295 154 140 117 106 100 89 70 61 51 51 41
KD 09200 401 209 191 160 144 136 121 95 83 70 70 56

The table is based on 60% cross-section usage of the pipes.



© 2017 KOPOS KOLÍN a.s., Jan Vrzáček